Nominal wattage | 27.00 W |
Nominal output power | 27 W 1) |
Nominal voltage | 220…240 V |
Nominal output voltage | 12…54 V 2) |
Input voltage AC | 198…264 V 3) |
Input voltage DC | 176…276 V |
U-OUT (working voltage) | 60 V |
Nominal current | 0.14 A |
Nominal output current | 180…700 mA 4) |
Inrush current |
|
Output current tolerance | ±3 % |
Output ripple current (100 Hz) | < 1 % 6) |
Mains frequency | 0/50/60 Hz |
Total harmonic distortion | < 20 % 7) |
Power factor λ | > 0.95 |
ECG efficiency | 88 % 8) |
Device power loss | 4,5 W |
Max. ECG no. on circuit breaker 10 A (B) | 50 |
Max. ECG no. on circuit breaker 16 A (B) | 80 |
Max. ECG no. on circuit breaker 25 A (B) | - |
Surge capability (L/N-Ground) | 2 kV |
Surge capability (L-N) | 1 kV |
Power loss in stand-by mode | < 0.1 W |
Flickering metric (Pst LM) | ≤1 |
Flickering metric (Pst LM) | ≤1 |
Stroboscope effect metric (SVM) | ≤0.4 |
Length | 103.00 mm |
Mounting hole spacing, length | 94,0 mm |
Width | 67.00 mm |
Height | 29.50 mm |
Cable cross-section, input side | 0.2…1.5 mm² 1) |
Cable cross-section, output side | 0.2…1.5 mm² 1) |
Wire preparation length, input side | 8.0…9.0 mm |
Wire preparation length, output side | 8.0…9.0 mm |
Product weight | 149.00 g |
Product color | White |
Casing material | Plastic |
Body material | Plastic |
Ambient temperature range | -20…+50 °C |
Maximum temperature at tc test point | 75 °C 1) |
Max.housing temperature in case of fault | 110 °C |
Permitted rel. humidity during operation | 5…85 % 2) |
ECG lifetime | 50000 h, 100000 h 1) |
Encapsulated | No |
Dimmable | Yes |
Dimming interface | DALI, Touch DIM, Touch DIM Sensor |
Dimming range | 1…100 % 1) |
Overheating protection | Automatic reversible |
Overload protection | Automatic reversible |
Short-circuit protection | Automatic reversible |
No-load proof | Yes |
Max. cable length to lamp/LED module | 2,0 m |
Suitable for fixtures with prot. class | I, II |
Suitable for emergency lighting | Yes |
Type of connection, output side | Push terminal |
Approval marks – approval | ENEC 10, VDE, EMC, EL, CE, DALI-2, BIS |
Standards | Acc. to EN 61347-1, Acc. to EN 61347-2-13, Acc. to EN 55015, Acc. to EN 61547, Acc. to EN 61000-3-2, Acc. to EN 62384, Acc. to EN 62386, Acc. to IEC 62386-101:Ed2, Acc. to IEC 62386-102:Ed2, Acc. to IEC 62386-207:Ed1 |
Protection class | II |
Type of protection | IP20 |
Temperature range at storage | -25…85 °C |
Networked standby power for CLS | ≤0.15 W |
Quantity of precious metals | 0 mg |
Quantity of rare earths | 0 mg |
Minimum rate of recycled material in packaging | 80 % 1) |
Minimum percentage of recycled content in the product | 0 % 1) |
Product recyclability | Mostly recyclable product 1) |
Packaging recyclability | Mostly recyclable packaging 1) |
List of dangerous substances contained in the product in concentrations greater than 0.1% in mass percentage | No |
Contains substances of very high concern in concentrations greater than 0.1% by mass percentage | Yes |
List of substances of very high concern in concentrations greater than 0.1% in mass percentage | Lead (7439-92-1) |
Product code | Packaging unit (Pieces/Unit) | Dimensions (length x width x height) | Gross weight | Volume |
---|---|---|---|---|
4052899488144 | Unpacked 1 |
149.00 g | ||
4052899488151 | Shipping box 20 |
357 mm x 222 mm x 96 mm | 3231.00 g | 7.61 dm³ |
EAN | SEG number | STK number | ELDAS number |
---|---|---|---|
4052899488144 | 7981820 | 4030357 | 941796300 |