PTi 150/220…240 I

Product family benefits
  • Extended terminal section enables mains looping
  • Screw-down cable clamps for reliable strain relief
  • Long reliable life at maximum permitted temperatures
  • Automatic safety shutdown of lamps in the event of a defect or at end of life (EoL)

Product details

Electrical data

Lamp wattage 147 W
Line current
0.72 A
Ignition voltage 4.5 kVp
Operating frequency 0.165 kHz
System wattage [AGGR] 160.00 W
ECG efficiency 92 %
Input voltage AC 198…254 V
Nominal voltage 220…240 V
Mains frequency 50…60 Hz
Power factor λ
0.95
Inrush current
70 A
Max. ECG no. on circuit breaker 10 A (B)
4
Max. ECG no. on circuit breaker 16 A (B)
7
Max. no. of ECGs on 16A MCB with EBN-OS
17
Protective conductor current 0.4 mA
U-OUT (working voltage) 250 V
Max. working voltage between LH and LL 250 V
Max. working voltage betw. LL/LH & earth 250 V
Max. capacitance of wire ECG/lamp 120 pF

Dimensions & weight

Length 212.0 mm
Width 93.0 mm
Height 33.0 mm
Mounting hole spacing, length 203.0 mm
Cable cross-section, input side 0.75…2.5 mm²
Cable cross-section, output side 0.75…2.5 mm²
Wire preparation length, input side 10…11 mm
Wire preparation length, output side 10…11 mm
Product weight 420.00 g

Colors & materials

Casing material Plastic

Temperatures & operating conditions

Ambient temperature range -25…+50 °C
Maximum temperature at tc test point 75 °C

Lifespan

ECG lifetime
40000 h

Additional product data

Design / version With cable clamp

Capabilities

Max. cable length to lamp/LED module 1.5 m
Overheating protection Power reduction and switch off at T > 75 °C at the tc point
ECG reset time > 0.5 s
Cable/wire types, input side NYM-J 3x1.5 / NYM-J 3x2.5 / H05VV-F 3x1.5 / NHXMH-J 3x1.5 mm²
Cable/wire types, output side SIHF-J 3x1.5 / SIHF-J 3x2.5 / SIHSI 3x1.0 mm²
Dimmable No
Restriction on ignition time 20 min
Suitable for fixtures with prot. class I

Certificates & standards

Approval marks – approval ENEC 10 / VDE / VDE-EMC / EAC / C-Tick
Type of protection IP20
EEI – Energy Label A2
Standards Acc. to EN 61347-2-12/Acc. to EN 55015/Acc. to EN 61000-3-2/Acc. to EN 61547/Acc. to EN 62493
Product code Packaging unit
Piece / unit
Dimensions in h x w x l Gross weight Volume
4008321915535 UNV
1
205mm x 91mm x 33mm 420.00g 0.62dm³
4008321915542 VS
20
488mm x 100mm x 453mm 9440.00g 22.11dm³
EAN METEL code SEG number STK number EFO number ELDAS number
4008321915535 OSRPTI150I 7980292 4030189 3322291 919572110
Product family benefits
  • Extended terminal section enables mains looping
  • Screw-down cable clamps for reliable strain relief
  • Long reliable life at maximum permitted temperatures
  • Automatic safety shutdown of lamps in the event of a defect or at end of life (EoL)
Areas of application
  • Shop lighting
  • Health and fitness areas (in luminaires with protection class IP66 or higher)
  • Effect and accent lighting
Product family features
  • Energy Efficiency Index EEI: A2
  • Supply voltage: 220…240 V
  • Line frequency: 50…60 Hz
  • RI suppression: to EN 55015/CISPR 15
  • Safety: to EN 61347-2-12
  • Line harmonics according to EN 61000-3-2
  • Immunity according to EN 61547

Safety advice
Ballast losses and lamp heat radiation can lead to heat accumulation in a completely closed case. Therefore it is necessary to ensure that the temperature at the measuring point t of the ECG does not exceed the maximum value.
Attention!
For safety reasons disconnect the device before replacing the lamp!