PT-FIT 70/220…240 I

Product benefits
  • ECG with ergonomic strain relief for correct installation in suspended ceilings
  • Optimized cost/benefit factor
  • Automatic safety shutdown of lamps in the event of a defect or at end of life (EoL)

Product details

Electrical data

Lamp wattage 73 W
Line current
0.36 A
Ignition voltage 4.5 kVp
Operating frequency 0.200…0.240 kHz
System wattage [AGGR] 80.00 W
ECG efficiency 92 %
Input voltage AC 198…264 V
Nominal voltage 220…240 V
Mains frequency 50…60 Hz
Power factor λ
0.95
Inrush current
45 A
Max. ECG no. on circuit breaker 10 A (B)
7
Max. ECG no. on circuit breaker 16 A (B)
13
Max. no. of ECGs on 16A MCB with EBN-OS
32
Protective conductor current 0.3 mA
U-OUT (working voltage) 250 V
Max. working voltage between LH and LL 250 V
Max. working voltage betw. LL/LH & earth 250 V
Max. capacitance of wire ECG/lamp 120 pF

Dimensions & weight

Length 172.0 mm
Width 83.0 mm
Height 33.0 mm
Mounting hole spacing, length 163.0 mm
Cable cross-section, input side
0.75…1.5 / 0.75…2.5 mm²
Cable cross-section, output side
0.75…1.5 / 0.75…2.5 mm²
Wire preparation length, input side 5.5…6.5 mm
Wire preparation length, output side 5.5…6.5 mm
Product weight 290.00 g

Colors & materials

Casing material Plastic

Temperatures & operating conditions

Ambient temperature range -15…+45 °C
Maximum temperature at tc test point 75 °C

Lifespan

ECG lifetime
30000 h

Additional product data

Design / version With cable clamp

Capabilities

Max. cable length to lamp/LED module 1.5 m
Overheating protection Power reduction and switch off at T > 75 °C at the tc point
ECG reset time > 0.5 s
Cable/wire types, input side NYM-J 3x1.5 / NYM-J 3x2.5 / H05VV-F 3x1.5 / NHXMH-J 3x1.5 mm²
Cable/wire types, output side SIHF-J 3x1.5 / SIHF-J 3x2.5 / SIHSI 3x1.0 mm²
Dimmable No
Restriction on ignition time 20 min
Suitable for fixtures with prot. class I

Certificates & standards

Approval marks – approval VDE / VDE-EMC / EAC / C-Tick
Type of protection IP20
EEI – Energy Label A2
Standards Acc. to EN 61347-2-12/Acc. to EN 55015/Acc. to EN 61000-3-2/Acc. to EN 61547/Acc. to EN 62493
Product code Packaging unit
Piece / unit
Dimensions in h x w x l Gross weight Volume
4008321377685 UNV
1
167mm x 33mm x 83mm 290.00g 0.46dm³
4008321377692 VS
20
437mm x 100mm x 406mm 6582.00g 17.74dm³
EAN SEG number EFO number
4008321377685 7980323 3322005
Product benefits
  • ECG with ergonomic strain relief for correct installation in suspended ceilings
  • Optimized cost/benefit factor
  • Automatic safety shutdown of lamps in the event of a defect or at end of life (EoL)
Areas of application
  • Shop lighting
  • Health and fitness areas (in dry, corrosion-protected place)
  • Effect and accent lighting
Product features
  • Energy Efficiency Index EEI: A2
  • Supply voltage: 220…240 V
  • Line frequency: 50…60 Hz
  • RI suppression: to EN 55015/CISPR 15
  • Safety: to EN 61347-2-12
  • Line harmonics according to EN 61000-3-2
  • Immunity according to EN 61547

Thermal characteristics
Ballast losses and lamp heat radiation can lead to heat accumulation in a completely closed case. Therefore it is necessary to ensure that the temperature at the measuring point tc of the ECG does not exceed the maximum value.
Attention!
For safety reasons disconnect the device before replacing the lamp!