Overview POWERTRONIC INTELLIGENT PTi S

Product description Lamp wattage Line current Ignition voltage Operating frequency Ambient temperature range
PTi 35/220…240 S 39W 0.19A 4.5kVp 0.200…0.240kHz -25…+65°C
PTi 35/220…240 S MINI 39W 0.19A 3.0kVp 0.100…0.120kHz -25…+50°C
PTi 50/220…240 S 50W 0.24A 4.5kVp 0.200…0.240kHz -25…+60°C
PTi 70/220…240 S 73W 0.36A 4.5kVp 0.200…0.240kHz -25…+55°C
PTi 150/220…240 S 147W 0.72A 4.5kVp 0.165kHz -25…+55°C
 

PTi 35/220…240 S MINI

Product family benefits
  • Long reliable life at maximum permitted temperatures
  • Compact dimensions and low weight for small luminaire designs
  • Excellent thermal behavior for very high limit temperatures tc and ta
  • Automatic safety shutdown of lamps in the event of a defect or at end of life (EoL)

Product details

Electrical data

Lamp wattage 39 W
Line current
0.19 A
Ignition voltage 3.0 kVp
Operating frequency 0.100…0.120 kHz
System wattage [AGGR] 43.00 W
ECG efficiency 90 %
Input voltage AC 198…264 V
Nominal voltage 220…240 V
Mains frequency 50…60 Hz
Power factor λ
0.95
Inrush current
20 A
Max. ECG no. on circuit breaker 10 A (B)
17
Max. ECG no. on circuit breaker 16 A (B)
28
Max. no. of ECGs on 16A MCB with EBN-OS
70
Protective conductor current 0.1 mA
U-OUT (working voltage) 250 V
Max. working voltage between LH and LL 250 V
Max. working voltage betw. LL/LH & earth 250 V
Max. capacitance of wire ECG/lamp 40 pF

Dimensions & weight

Length 97.0 mm
Width 43.0 mm
Height 30.0 mm
Mounting hole spacing, length 88.0 mm
Mounting hole spacing, width 34.0 mm
Cable cross-section, input side 0.5…1.5 mm²
Cable cross-section, output side 0.5…1.5 mm²
Wire preparation length, input side 8.5…9.5 mm
Wire preparation length, output side 8.5…9.5 mm
Product weight 105.00 g

Colors & materials

Casing material Plastic

Temperatures & operating conditions

Ambient temperature range -25…+50 °C
Maximum temperature at tc test point 80 °C

Lifespan

ECG lifetime
50000 h

Additional product data

Design / version Built-in unit

Capabilities

Max. cable length to lamp/LED module 0.5 m
Overheating protection Power reduction and switch off at T > 80 °C at the tc point
ECG reset time > 0.5 s
Dimmable No
Restriction on ignition time 20 min
Suitable for fixtures with prot. class I / II

Certificates & standards

Approval marks – approval ENEC 10 / VDE / VDE-EMC / EAC / C-Tick
Type of protection IP20
EEI – Energy Label A2
Standards Acc. to EN 61347-2-12/Acc. to EN 55015/Acc. to EN 61000-3-2/Acc. to EN 61547
Product code Packaging unit
Piece / unit
Dimensions in h x w x l Gross weight Volume
4008321955906 UNV
1
98mm x 42mm x 31mm 105.00g 0.13dm³
4008321955982 VS
20
228mm x 78mm x 208mm 2106.00g 3.70dm³
EAN METEL code SEG number STK number EFO number ELDAS number
4008321955906 OSRPTI35SM 7980343 4030087 3322137 919571400
Product family benefits
  • Long reliable life at maximum permitted temperatures
  • Compact dimensions and low weight for small luminaire designs
  • Excellent thermal behavior for very high limit temperatures tc and ta
  • Automatic safety shutdown of lamps in the event of a defect or at end of life (EoL)
Areas of application
  • Shop lighting
  • Health and fitness areas (in luminaires with protection class IP66 or higher)
  • Effect and accent lighting
Product family features
  • Energy Efficiency Index EEI: A2
  • Supply voltage: 220…240 V
  • Line frequency: 50…60 Hz
  • RI suppression: to EN 55015/CISPR 15
  • Safety: to EN 61347-2-12
  • Line harmonics according to EN 61000-3-2
  • Immunity according to EN 61547

Safety advice
Ballast losses and lamp heat radiation can lead to heat accumulation in a completely closed case. Therefore it is necessary to ensure that the temperature at the measuring point t of the ECG does not exceed the maximum value.
Attention!
For safety reasons disconnect the device before replacing the lamp!
Any conductive material must have a minimum distance of 4 mm to the front of the terminal block.
Installation by qualified electrician only.