Professional
Country

QUICKTRONIC PROFESSIONAL OPTIMAL

Choose your product version

Overview QUICKTRONIC PROFESSIONAL OPTIMAL

Product description Ambient temperature range Input voltage AC Nominal voltage Mains frequency Input voltage DC
QTP-OPTIMAL 1X18…40 -20…+50°C 198…264V 220…240V 50…60Hz 176…276V
QTP-OPTIMAL 1X54…58 -20…+50°C 198…264V 220…240V 50…60Hz 176…276V
QTP-OPTIMAL 2X18…40 -20…+50°C 198…264V 220…240V 50…60Hz 176…276V
QTP-OPTIMAL 2X54…58 -20…+50°C 198…264V 220…240V 50…60Hz 176…276V
 

QTP-OPTIMAL 2X54…58

Product family benefits
  • Long lamp life
  • No adverse effect from frequent on/off switching
  • Automatic restart after lamp replacement
  • Perfect lamp start for applications with motion sensors
  • VDE/VDE EMC certified system
  • Very high energy efficiency due to cut-off technology

Product details

Nominal current 0.48 A
Nominal wattage + Power loss 110.00 W
Luminous flux at 35 °C 4800 lm
Number of lighting outlets 2
ECG_1.1 Ambient temperature for lifespan 40 °C
ECG_1.2 Ambient temperature for lifespan 50 °C
ECG_1.3 Ambient temperature for lifespan 60 °C
ECG_2.1 Tc point temperature for lifespa 55 °C
ECG_2.2 Tc point temperature for lifespa 65 °C
ECG_2.3 Tc point temperature for lifespa 75 °C
ECG_3.1 Temperature dependent lifespan 100000 h
ECG_3.2 Temperature dependent lifespan 100000 h
ECG_3.3 Temperature dependent lifespan 60000 h
Nominal current 0.46 A
Nominal wattage + Power loss 107.00 W
Luminous flux at 35 °C 4450 lm
Number of lighting outlets 2
Nominal current 0.52 A
Nominal wattage + Power loss 120.00 W
Luminous flux at 35 °C 4450 lm
Number of lighting outlets 2
ECG_1.1 Ambient temperature for lifespan 40 °C
ECG_1.2 Ambient temperature for lifespan 50 °C
ECG_1.3 Ambient temperature for lifespan 60 °C
ECG_2.1 Tc point temperature for lifespa 60 °C
ECG_2.2 Tc point temperature for lifespa 65 °C
ECG_2.3 Tc point temperature for lifespa 75 °C
ECG_3.1 Temperature dependent lifespan 100000 h
ECG_3.2 Temperature dependent lifespan 90000 h
ECG_3.3 Temperature dependent lifespan 50000 h
Nominal current 0.52 A
Nominal wattage + Power loss 120.00 W
Luminous flux at 35 °C 4450 lm
Number of lighting outlets 2
Nominal current 0.49 A
Nominal wattage + Power loss 112.00 W
Luminous flux at 35 °C 5000 lm
Number of lighting outlets 2
ECG_1.1 Ambient temperature for lifespan 40 °C
ECG_1.2 Ambient temperature for lifespan 50 °C
ECG_1.3 Ambient temperature for lifespan 60 °C
ECG_2.1 Tc point temperature for lifespa 55 °C
ECG_2.2 Tc point temperature for lifespa 65 °C
ECG_2.3 Tc point temperature for lifespa 75 °C
ECG_3.1 Temperature dependent lifespan 100000 h
ECG_3.2 Temperature dependent lifespan 100000 h
ECG_3.3 Temperature dependent lifespan 60000 h
Nominal current 0.49 A
Nominal wattage + Power loss 112.00 W
Luminous flux at 35 °C 5000 lm
Number of lighting outlets 2

Electrical data

Input voltage AC 198…264 V
Nominal voltage 220…240 V
Mains frequency 50…60 Hz
Input voltage DC 176…276 V
Operating frequency 40…50 kHz
Max. ECG no. on circuit breaker 10 A (B)
8
Max. ECG no. on circuit breaker 16 A (B)
13
Inrush current 57 A

Light technical data

Starting time 1.5 s

Dimensions & weight

Length 360.0 mm
Width 30.0 mm
Height 21.0 mm
Mounting hole spacing, length 350.0 mm
Product weight 239.90 g

Temperatures & operating conditions

Ambient temperature range -20…+50 °C
Permitted rel. humidity during operation
5…85 %

Lifespan

ECG lifetime
100000 h

Capabilities

Suitable for fixtures with prot. class I / II
End of lamp life safety shutdown EOL T.2

Certificates & standards

Approval marks – approval EL / VDE / ENEC 10 / VDE-EMC
EEI – Energy Label A2 BAT
Standards Acc. to IEC 61347-2-3 / App. J/Acc. to EN 55015:2006 + A1:2007 + A2:2009/Acc. to EN 61000-3-2/Acc. to EN 61547
Protection class I/II
Type of protection IP20
Product code Packaging unit
Piece / unit
Dimensions in h x w x l Gross weight Volume
4008321880253 UNV
1
239.90g
4008321880260 VS
20
385mm x 160mm x 100mm 4969.00g 6.16dm³
EAN SEG number STK number EFO number ELDAS number
4008321880253 7980723 4030271 3359232 919444470
Product family benefits
  • Long lamp life
  • No adverse effect from frequent on/off switching
  • Automatic restart after lamp replacement
  • Perfect lamp start for applications with motion sensors
  • VDE/VDE EMC certified system
  • Very high energy efficiency due to cut-off technology
Areas of application
  • Emergency lighting systems acc. to EN 50172 / DIN VDE 0108-100
  • Industry
  • Open-plan offices, corridors and storage rooms
  • Public buildings
  • Sports halls and factories
  • Strip lighting
  • Suitable for emergency lighting (DC operation)
  • Modernization of existing systems
  • Suitable for luminaires of protection classes I and II
Product family features
  • Supply voltage: 220…240 V
  • Line voltage: 198…264 V
  • Line frequency: 0 Hz | 50 Hz | 60 Hz
  • Lamp start with optimum filament preheating
  • Lifetime: up to 100,000 h (temperature at Tc = 65 °C, max. 10 % failure rate)
  • Energy Efficiency Index EEI: A2 BAT
  • Automatic shutdown of defective lamps and at end of life (EoL T.2)
  • Safety: to EN 61347-2-3
  • Lamp operation: to EN 60929