Professional
Country

QUICKTRONIC FIT 5

Choose your product version

Overview QUICKTRONIC FIT 5

Product description Ambient temperature range Input voltage AC Nominal voltage Mains frequency Input voltage DC
QT-FIT5 1X14…35 -15…+50°C 198…264V 220…240V 50…60Hz 185…264V
QT-FIT5 2X14…35 -15…+50°C 220…240V 50…60Hz 198…264V
QT-FIT5 3X14,4X14 -15…+50°C 198…264V 220…240V 50…60Hz 185…264V
QT-FIT5 1X49 -15…+50°C 198…264V 220…240V 50…60Hz 186…276V
QT-FIT5 2X49 -15…+50°C 198…264V 220…240V 50…60Hz 185…264V
 

QT-FIT5 2X49

Product family benefits
  • Long lamp life
  • No adverse effect from frequent on/off switching
  • Automatic restart after lamp replacement
  • Perfect lamp start for applications with motion sensors
  • VDE/VDE EMC certified system
  • Very high energy efficiency due to cut-off technology

Product details

Nominal current 0.43 A
Nominal wattage + Power loss 98.00 W
Luminous flux at 35 °C 4300 lm
Number of lighting outlets 2
ECG_1.1 Ambient temperature for lifespan 40 °C
ECG_1.2 Ambient temperature for lifespan 50 °C
ECG_1.3 Ambient temperature for lifespan 60 °C
ECG_2.1 Tc point temperature for lifespa 60 °C
ECG_2.2 Tc point temperature for lifespa 65 °C
ECG_2.3 Tc point temperature for lifespa 75 °C
ECG_3.1 Temperature dependent lifespan 100000 h
ECG_3.2 Temperature dependent lifespan 90000 h
ECG_3.3 Temperature dependent lifespan 50000 h
Nominal current 0.47 A
Nominal wattage + Power loss 106.00 W
Luminous flux at 35 °C 4300 lm
Number of lighting outlets 2
ECG_1.1 Ambient temperature for lifespan 40 °C
ECG_1.2 Ambient temperature for lifespan 50 °C
ECG_1.3 Ambient temperature for lifespan 56 °C
ECG_2.1 Tc point temperature for lifespa 65 °C
ECG_2.2 Tc point temperature for lifespa 70 °C
ECG_2.3 Tc point temperature for lifespa 75 °C
ECG_3.1 Temperature dependent lifespan 100000 h
ECG_3.2 Temperature dependent lifespan 40000 h
ECG_3.3 Temperature dependent lifespan 50000 h

Electrical data

Input voltage AC 198…264 V
Nominal voltage 220…240 V
Mains frequency 50…60 Hz
Input voltage DC
185…264 V
Operating frequency 40…50 kHz
Max. ECG no. on circuit breaker 10 A (B)
8
Max. ECG no. on circuit breaker 16 A (B)
13
Inrush current 53 A

Light technical data

Starting time 2.0 s

Dimensions & weight

Length 280.0 mm
Width 30.0 mm
Height 21.0 mm
Mounting hole spacing, length 270.0 mm
Product weight 185.00 g
Cable cross-section, output side
0.5…1.5 mm²
Cable cross-section, input side
0.5…1.5 mm²

Temperatures & operating conditions

Ambient temperature range -15…+50 °C
Permitted rel. humidity during operation
5…85 %

Lifespan

ECG lifetime 50000 h

Capabilities

Suitable for fixtures with prot. class I
End of lamp life safety shutdown EOL T.2

Certificates & standards

Approval marks – approval VDE / ENEC 10 / VDE-EMC
EEI – Energy Label A2 BAT
Standards Acc. to EN 61347-2-3/IEC 61347-2-3/Acc. to EN 55015:2006 + A1:2007 + A2:2009/Acc. to EN 61000-3-2/IEC 61000-3-2/Acc. to EN 61547/IEC 61547
Protection class I/II
Type of protection IP20
Product code Packaging unit
Piece / unit
Dimensions in h x w x l Gross weight Volume
4008321832153 UNV
1
185.00g
4008321832160 VS
20
312mm x 98mm x 165mm 3841.00g 5.05dm³
EAN STK number EFO number
4008321832153 4030226 3351159
Product family benefits
  • Long lamp life
  • No adverse effect from frequent on/off switching
  • Automatic restart after lamp replacement
  • Perfect lamp start for applications with motion sensors
  • VDE/VDE EMC certified system
  • Very high energy efficiency due to cut-off technology
Areas of application
  • Open-plan offices, corridors and storage rooms
  • Public buildings
  • Strip lighting
  • Suitable for emergency lighting (DC operation)
  • Suitable for luminaires of protection class I
  • Modernization of existing systems
Product family features
  • Supply voltage: 220…240 V
  • Line voltage: 198…264 V
  • Line frequency: 50 Hz | 60 Hz
  • Lamp start with optimum filament preheating
  • Energy Efficiency Index EEI: A2
  • Automatic shutdown of defective lamps and at end of life (EoL T.2)
  • Lamp operation: to EN 60929
  • Safety: to EN 61347-2-3