Professional
Country

OPTOTRONIC ECO

Choose your product version

Overview OPTOTRONIC ECO

Product description Nominal voltage Mains frequency Input voltage AC Total harmonic distortion Power factor λ
OTe 35/220…240/700 CS 220…240V 50…60Hz 195…264V < 20% 0.95
OTe 35/220…240/1A0 CS 220…240V 50…60Hz 195…264V < 20% 0.95
OTe 35/220…240/1A0 CS S 220…240V 50…60Hz 195…264V < 20% 0.95
OTe 50/220…240/1A4 CS 220…240V 50…60Hz 198…264V < 20% 0.95
 

OTe 35/220…240/1A0 CS S

Product family benefits
  • Versatile scope of application due to output power range of up to 54 W
  • Efficient and reliable

Product details

Electrical data

Nominal voltage 220…240 V
Mains frequency 50…60 Hz
Input voltage AC
195…264 V
Total harmonic distortion < 20 %
Power factor λ
0.95
ECG efficiency
87 %
Device power loss
5.5 W
Inrush current
16 A
Max. ECG no. on circuit breaker 10 A (B) 28
Max. ECG no. on circuit breaker 16 A (B) 44
Max. ECG no. on circuit breaker 25 A (B) -
Surge capability (L/N-Ground) 1 kV
Surge capability (L-N) 1 kV
Nominal output voltage
17…34 V
U-OUT (working voltage) 50 V
Nominal output current
800 / 925 / 1050 mA
Output current tolerance ±5 %
Nominal output power
36 W
Galvanic isolation SELV
Galvanic isolation primary/secondary
3.75 kV

Dimensions & weight

Length 110.0 mm
Width 43.0 mm
Height 29.5 mm
Mounting hole spacing, length 101.0 mm
Mounting hole spacing, width 34.0 mm
Cable cross-section, input side 0.5…1.5 mm²
Cable cross-section, output side 0.5…1.5 mm²
Product weight 135.00 g
Wire preparation length, input side 8.0…9.0 mm
Wire preparation length, output side 8.0…9.0 mm

Colors & materials

Casing material Plastic

Temperatures & operating conditions

Ambient temperature range -20…+50 °C
Maximum temperature at tc test point
80 °C
Max.housing temperature in case of fault 110 °C
Permitted rel. humidity during operation
5…85 %

Lifespan

ECG lifetime
50000 h

Additional product data

Encapsulated No

Capabilities

Dimmable No
Overheating protection Automatic reversible
Overload protection Automatic reversible
Short-circuit protection Automatic reversible
No-load proof Yes
Max. cable length to lamp/LED module 2.0 m
Suitable for fixtures with prot. class I / II
Type of connection, output side Push terminal

Certificates & standards

Approval marks – approval ENEC 10 / VDE / CE
Standards Acc. to IEC 61347-1/Acc. to IEC 61347-2-13/Acc. to IEC 62384/Acc. to CISPR 15/Acc. to IEC 61000-3-2/Acc. to IEC 61547/Acc. to IEC 61000-3-3
Type of protection IP20

Logistical data

Temperature range at storage -25…75 °C
Product code Packaging unit
Piece / unit
Dimensions in h x w x l Gross weight Volume
4052899917651 UNV
1
135.00g
4052899917675 VS
20
239mm x 232mm x 93mm 2974.00g 5.16dm³
Product family benefits
  • Versatile scope of application due to output power range of up to 54 W
  • Efficient and reliable
Areas of application
  • Suitable for use in luminaires with flexible current setting (Tri-Tap)
  • Suitable for indoor SELV installations
  • Suitable for luminaires of protection classes I and II
  • Suitable for downlights, spotlights and LED panels
  • Independent mounting via Cable Clamp Kit possible
Product family features
  • Supply voltage: 220…240 V
  • Line frequency: 50 Hz | 60 Hz
  • Line voltage: 198…264 V
  • According to EN 61347-1, 61347-2-13, 62384
  • RI suppression according to EN 55015:2007+A1:2007/CDN
  • Line harmonics according to EN 61000-3-2
  • Immunity according to EN 61547
  • Lifetime: up to 50,000 h
  • Independent connection via through-looping (depending on version of product)