Product description | Length | Width | Height | Product weight | Prewired |
---|---|---|---|---|---|
OTi DALI 10/220 240/700 NFC | 124.0mm | 31.0mm | 21.0mm | 50.00g | |
OTi DALI 50/220...240/1A4 LT2 FAN NFC | 110.0mm | 75.0mm | 25.0mm | 180.00g |
Nominal voltage | 220 240 V |
Mains frequency | 0 60 Hz |
Input voltage AC |
198
264 V
|
Input voltage DC | 176 276 V |
Total harmonic distortion |
15 %
|
Power factor λ | > 0.98/> 0.94 |
ECG efficiency |
82 %
|
Device power loss | 3.5 W |
Power loss in stand-by mode | ≤0.15 W |
Inrush current |
< 5 A
|
Max. ECG no. on circuit breaker 10 A (B) | 80 |
Max. ECG no. on circuit breaker 16 A (B) | 130 |
Max. ECG no. on circuit breaker 25 A (B) | - |
Surge capability (L/N-Ground) | 2 kV |
Surge capability (L-N) | 1 kV |
Nominal output voltage |
2.5
45 V
|
U-OUT (working voltage) | 60 V |
Nominal output current |
150
700 mA
|
Output current tolerance | ±3 % |
Output ripple current (100 Hz) | < 2 % |
Nominal output power |
10 W
|
Galvanic isolation | SELV |
Galvanic isolation primary/secondary | 3.75 kV |
Length | 124.0 mm |
Width | 31.0 mm |
Height | 21.0 mm |
Mounting hole spacing, length | 115.0 mm |
Cable cross-section, input side |
0.2
1.5 mm²
|
Cable cross-section, output side |
0.2
1.5 mm²
|
Product weight | 50.00 g |
Wire preparation length, input side | 8.0 9.1 mm |
Wire preparation length, output side | 8.0 9.1 mm |
Casing material | Plastic |
Ambient temperature range | -20 +50 °C |
Maximum temperature at tc test point |
75 °C
|
Max.housing temperature in case of fault | 110 °C |
Permitted rel. humidity during operation |
5
85 %
|
ECG lifetime |
50000 / 100000 h
|
Encapsulated | No |
Dimmable | Yes |
Dimming interface | DALI |
Dimming range |
1
100 %
|
Dimming method | Amplitude Modulation |
Constant lumen function | Programmable |
Overheating protection | Automatic reversible |
Overload protection | Automatic reversible |
Short-circuit protection | Automatic reversible |
No-load proof | Yes |
Max. cable length to lamp/LED module | 2.0 m |
Suitable for fixtures with prot. class | I / II |
Suitable for emergency lighting | Yes |
Type of connection, output side | Push terminal |
Approval marks – approval | ENEC 10 / VDE / EMC / EL / CE / DALI-2 / CCC |
Standards | Acc. to EN 61347-1/Acc. to EN 61347-2-13/Acc. to EN 55015/Acc. to EN 61547/Acc. to EN 61000-3-2/Acc. to EN 62384/Acc. to EN 62386/Acc. to IEC 62386-101:Ed2/Acc. to IEC 62386-102:Ed2/Acc. to IEC 62386-207:Ed1 |
Protection class | II |
Type of protection | IP20 |
Temperature range at storage | -40 +85 °C |
Product code | Packaging unit Piece / unit |
Dimensions in h x w x l | Gross weight | Volume |
---|---|---|---|---|
4052899562639 | UNV 1 |
|||
4052899562646 | VS 20 |
165mm x 258mm x 71mm | 1120.00g | 3.02dm³ |